Leak testing
This is testing to support the frequent thorough visual inspections of the
enclosure as described in EH51. 11A number of sample positions should be
considered: for example, near an air lock, near a gag-lock, and near the
exhausts of negative pressure units. For this type of testing it may be
possible only to sample for a few minutes, in which case a high flowrate
should be used and the cause of any fibres above background should be investigated.
If fewer than 20 fibres are counted, or less than 480 litres of air is
sampled, then a calculated result greater than 0.01 f/ml will have a large
imprecision and account must be taken of this by proportionally increasing
the limit of detection.
Personal sampling to assess respiratory protection
This can be achieved by personal sampling with the pump attached to the respirator
belt and the filter holder attached to the hood of the wearer’s overall.
Airborne fibre concentrations may vary from the detection limit of 0.01f/ml
up to a level in excess of 650 f/ml (if dust control is poor)
Clearance indicator sampling (clearance testing)
Clearance indicator sampling should take place only when the enclosure is dry
and a visual inspection confirms that it is free from dust. 6 Practical advice
on the preparation of the enclosure, and application of clearance tests, is
given in Guidance Notes. 11,22 The filter holders should point downwards, be
fixed 1-2 m from the floor and be distributed throughout the enclosure. In
tall enclosures (for example, vertical pipework or lift shafts), samplers should
be placed at representative exposure heights, especially in areas where residual
dust may be difficult to detect. There should always be at least two measurements
(unless the volume of the enclosure is less than 10 m 3, in which case one
measurement is adequate). With that overriding condition, the number of samples
should be at least the integer (whole number) next below (A 1/3 –1) where
A is determined as follows.
a) if the enclosure is less than or equal to 3 m in height, or in enclosures
which are higher than 3 m but where exposure is likely to be at ground level
only, A is the area of the enclosure in square metres;
b) in other cases, A is one-third of the enclosure volume in cubic metres;
if there are large items of plant (such as boilers) in the enclosure,
their volumes may be subtracted from the gross volumes before calculating
A. |